Hospital ward with monitored beds
Hospitals and healthcare

Hospitals that hold air, water and uptime in range.

Wards, theaters and plant rooms on one platform. Aqueduct can replace or connect the BMS and water systems a hospital runs, act on faults, and verify the result, with the records infection control and accreditation ask for.

Hall B · occupied
1,184 ppm CO₂
Ventilation adjusted
Demo data
AHU-1 · fault
Supply fan stopped08:02
Failed rotor shaft08:03
Routed to CMMS08:04
Airflow confirmed11:40
Demo data

Keep wards, theaters and plant rooms in range, with records that stand up to inspection.

Water safety records

Outlet temperatures and flow, evidenced without a clipboard

  • Outlets and risers

    Temperature and flow are read continuously at outlets and risers, so the water management program has real records.

  • Low-use outlets flagged

    Outlets with little or no flow are flagged early, so flushing is planned before water sits too long.

  • Survey-ready history

    Every reading and every corrective action is retained, so the next survey sees evidence instead of memory.

Large pipelines through a forest
Water balance · live
42.6Supply=36.1Floors+4.2RO+2.3Loss
Unaccounted loss rising on line CW-4
Demo data
Air by clinical space

Theaters, isolation rooms and wards held to their targets

  • Targets by space type

    Each theater, isolation room and ward is measured against its own target, not a single building average.

  • Cause, not just alarm

    A CO2 rise is traced to the AHU and damper behind it, explained in plain language for the engineer.

  • Ventilation that responds

    Where control is enabled, with owner approval, ventilation is adjusted and the space is verified back in range.

Clean hospital corridor
Hall B · occupied
1,184 ppm CO₂
Ventilation adjusted
Demo data
Plant that never stops

Chillers, boilers and AHUs fixed before a ward notices

  • Faults diagnosed

    AHU, pump and chiller faults arrive with the likely cause and the fix, routed into your CMMS.

  • Early signs of failure

    Vibration, sound signature and energy drift on critical plant schedule maintenance before the failure reaches a ward.

  • Savings in money

    Plant energy is baselined against weather, and the difference is stated in money and confirmed at the meter.

Aerial view of rooftop chillers
Compressor 2 · condition
7.1 mm/s vibration
Maintenance scheduled before failure
Demo data
Old way vs the Aqueduct way

Running a hospital estate, before and after Aqueduct

The old way
  • Outlet temperatures are logged by hand on a weekly round.
  • A stuffy ward is found when a nurse calls facilities.
  • AHU faults are discovered when a theater drifts out of range.
  • Plant savings are promised in a proposal and never measured.
  • Survey preparation means weeks of gathering paper records.
The Aqueduct way
  • Outlet temperatures are read continuously and kept as evidence.
  • Ward CO2 rises, the cause is named, and ventilation responds.
  • AHU faults are diagnosed and routed before the theater drifts.
  • Plant savings are verified at the meter against a weather baseline.
  • Survey records are already there, space by space and day by day.
Problems by outcome

What hospitals and healthcare teams are up against.

Water, energy, air and operations carry equal weight. Each one runs the same loop: monitor, measure, identify, act, verify.

01

Water: Water safety you can evidence

Temperature and flow at outlets and risers, continuously, so the water management program has records instead of clipboards.

02

Energy: 24-hour plant, verified savings

Chillers, boilers and AHUs baselined against weather. Savings stated in money, confirmed at the meter.

03

Air: Pressure and air changes by space

Theaters, isolation rooms and wards held to their targets, with ventilation adjusted and verified back in range.

04

Operations: Faults fixed before a ward notices

AHU, pump and chiller faults diagnosed, ticketed into your CMMS and confirmed closed.

Problem, solution, impact

Problem, solution, impact.

How Aqueduct resolves each problem for hospitals and healthcare, and what changes when it does.

The problemHow Aqueduct solves itThe impact
Water

Temperature and flow at outlets and risers, continuously, so the water management program has records instead of clipboards.

A live water balance across meters and sub-meters localizes the loss, routes the fix and confirms it closed at the meter.

Loss found from the balance, not the bill, and every fix verified.

Energy

Chillers, boilers and AHUs baselined against weather. Savings stated in money, confirmed at the meter.

Weather-normalized baselines per building and asset show the waste in money; schedules and setpoints adjust where control is enabled.

Savings stated in money and confirmed at the meter, not estimated.

Air

Theaters, isolation rooms and wards held to their targets, with ventilation adjusted and verified back in range.

Air quality per zone, overlaid with occupancy, with ventilation raised when it matters and verified back in range.

Targets held during occupied hours, with the energy cost counted.

Operations

AHU, pump and chiller faults diagnosed, ticketed into your CMMS and confirmed closed.

Faults diagnosed in plain language and routed into your CMMS with the fix; early signs of failure schedule maintenance first.

Fewer reactive call-outs and closures confirmed by the equipment.

One incident, start to finish

One incident, from first signal to verified fix.

An illustrative example of the flywheel on a typical site.

Monitor

Ward and theater air sensors, AHU points, water outlet temperatures, existing or newly specified.

Measure

A baseline per ward, theater and asset. Targets by space type.

Identify

CO2 rising in Ward 2B. Cause: AHU-02 fresh-air damper at minimum.

Act

Ventilation adjusted where control is enabled, and a ticket routed to your CMMS with the fix.

Verify

Ward 2B back in range in 14 minutes. The record is retained for the next survey.

Connected products

Four connected products on one data layer.

aQ WaterGuard

Find every leak and loss, fix it, prove it. Powered by aQ Core.

Learn more

aQ EnergySmart

Cut waste and demand, verified at the meter. Powered by aQ Core.

Learn more

aQ AirSafe

Hit air targets without burning energy. Powered by aQ Core.

Learn more

aQ PredictIQ

Faults fixed, failures prevented. Powered by aQ Core.

Learn more
Hospital atrium
What we believe

Patients should never feel the plant room, and the records should prove it.

Talk to our team
Replace or integrate

Replace what should be replaced. Connect the rest.

Replaces or works with your
  • BMS and BAS
  • Energy management
  • Indoor air quality monitoring
  • Water management
Integrates with your
  • CMMS
  • EAM
  • Nurse-call and clinical systems stay separate

Three equal ways in: keep your BMS, replace it, or build Aqueduct in at design stage.

Who it is for

The questions each seat asks first.

Director of facilities
“Does it fix things or just flag them?”
Infection prevention lead
“Can I show continuous records for water and air?”
CFO
“Is the saving measured or estimated?”
Standards and regulations

Standards and regulations we supply evidence for.

We supply the measured inputs. You run the program and file the report.

Clinical environment map

Eight spaces where the environment is part of care.

In most buildings a drifting utility costs money. In these rooms it becomes an infection control event or an accreditation finding. Each one has its own limits, its own way of failing quietly, and its own evidence trail.

01 / 08

Operating theaters: ready for the next case, or not

A theater holds positive pressure, filtered supply air and a humidity band through every case. Validation happens on a schedule, but pressure, air changes and filter loading drift between visits with nobody watching. Aqueduct turns the room's readings into one readiness state before the next patient arrives.

  • Per room, not per zone: each theater has its own control and its own record
  • Humidity rising past the upper limit shows up as a specific hold or proceed call
  • Filter differential trended, so the AHU is serviced before the room drifts
Measured
temperature, RH, room pair pressure, airflow, filter differential
Target
per ASHRAE 170 or your protocol
Aqueduct
aQ AirSafe readiness verdict per theater, retained as evidence
02 / 08

Neonatal intensive care: the room regulates for the baby

Newborns cannot hold their own temperature, so the room does it for them. The usual failure is slow thermal or humidity drift where no single reading looks wrong enough to flag. Trend scoring catches the direction of travel, not only the breach.

  • Temperature and humidity trended against the room's own band
  • CO2 and particulates logged alongside comfort conditions
  • The critical power feeding the unit on the same view
Measured
temperature, RH, CO2, PM2.5, UPS status
Target
per your standard
Aqueduct
drift alerts before the limit, plus a month's record on demand
03 / 08

Pediatric intensive care: climate and power together

The sickest children in the building need a stable climate and power that never blinks. Power readiness is often assumed until the day it is tested for real. Aqueduct shows room conditions and the UPS and generator behind them in one place.

  • UPS state of charge, transfer events and generator run tests recorded
  • Room conditions logged continuously rather than on rounds
  • One alert path when either the room or its power supply moves
Measured
room conditions, UPS, generator, feeder load
Target
per your standard
Aqueduct
aQ EnergySmart single line with critical loads flagged
04 / 08

Isolation: containment exists only while the differential holds

A negative pressure room protects corridors and staff only while air keeps moving the right way. A sticking damper, a loaded filter or a propped door can defeat it, and a wall gauge is only true while someone reads it. Aqueduct watches each room as a pair with its anteroom or corridor.

  • Differential pressure logged per room pair, continuously
  • Breach alerts that name the room, the duration and the likely cause
  • Door and damper context where those points exist
Measured
room pair differential pressure, exhaust airflow
Target
per ASHRAE 170 or your protocol
Aqueduct
containment status per room with a timestamped breach log
05 / 08

Dialysis: the one utility that reaches the bloodstream

Everywhere else, a water quality failure is an operations problem. On a dialysis line it is clinical. The ISO 23500 series expects ongoing monitoring of the treatment train, including online monitors such as conductivity, rather than only periodic tests.

  • RO performance trended between scheduled water tests
  • Conductivity and TDS watched at each stage of the train
  • Lab results stay with your renal team; Aqueduct holds the plant record
Measured
RO feed, permeate and reject, conductivity, TDS
Target
per your standard
Aqueduct
aQ WaterGuard treatment train view with drift alerts
06 / 08

Sterile services: a cascade, room to room

Instruments stay sterile because air moves from clean to less clean through a chain of rooms. That cascade is usually assumed from design rather than measured in use. Aqueduct records each room's conditions and the pressure relationship between neighbors.

  • Pressure relationships logged between each pair in the chain
  • Temperature and humidity for sterile stores
  • A cascade break shown as the link that failed, not seven alarms
Measured
room conditions, inter-room pressure
Target
per your standard
Aqueduct
cascade view with the failing link highlighted
07 / 08

Pharmacy and vaccine storage: catch it before the stock is lost

Controlled storage fails between checks, and the excursion is found after the product is already compromised. Continuous temperature per unit, with an exportable log, turns a discovery into an alert while there is still time to move stock.

  • Temperature per refrigerator, freezer and cold room
  • Door-open and compressor behavior where available
  • An excursion log the pharmacist can export for the record
Measured
unit temperature, compressor power
Target
per your standard
Aqueduct
alerts with time out of range and the affected unit
08 / 08

Central plant: the machinery behind every room above

Chillers, AHUs, UPS and generators sit behind every clinical space. Faults are usually found when a room drifts, which is too late. Aqueduct reads the plant and links it to the rooms it serves, so a coil fouling shows up as a risk to Theater 3 before Theater 3 moves.

  • Every AHU mapped to the rooms it supplies
  • Chiller efficiency and filter loading trended against load
  • aQ PredictIQ flags plant heading for failure while there is time to schedule it
Measured
chiller and AHU points, filter differential, UPS, feeders
Target
your plant baseline
Aqueduct
plant risk tied to clinical spaces, ticketed into your CMMS
Limits, as published

What ASHRAE 170 sets, and what your protocol sets.

These are design parameters from ANSI/ASHRAE/ASHE Standard 170 for two room types. Where we are not quoting the standard directly, the cell says per your standard. NABH and other accreditation limits are configured from your own protocol. Aqueduct holds the limits you set; it does not set clinical standards.

ParameterOperating roomAirborne infection isolation roomNICU, ICU and NABH aligned spaces
Temperature68 to 75 F (20 to 24 C)per your standardper your standard
Relative humidity20 to 60 percentper your standardper your standard
Pressure relationshipPositive to adjacent spacesNegative, at least 0.01 in. w.c. (2.5 Pa)per your standard
Minimum total air changes per hour2012per your standard
Minimum outdoor air changes per hour42per your standard
Room air exhausted directly outdoorsNot requiredYesper your standard
Recirculating room unitsNot permittedNot permittedper your standard
Filtrationper your standardper your standardper your standard
How it works

From seven readings to one verdict a surgeon can use.

01

Read what already exists

Room sensors, AHU points and pressure monitors are read from the BMS over BACnet or Modbus. Retrofit sensors go in only where a measurement is missing, scheduled around clinical activity.

02

Score each parameter against its own limit

Temperature, humidity, pressure, air changes, particulates and filter state are each scored against the room's configured band, and against their trend over the last hour.

03

Roll it into one room state

The theater is ready, at risk, or not ready. At risk means a parameter is heading for its limit. Not ready names the parameter and how long it has been out.

04

Trace the cause

Humidity high with everything else in band points to the humidifier or the cooling coil on the serving AHU. aQ Assistant answers in plain language and shows the series behind the answer.

05

Act and keep the record

A ticket goes to your CMMS with the cause attached. Where control is enabled, with owner approval, the AHU is adjusted. The excursion, the response and the recovery are stored as one evidence record.

Same sensors, different question

Your BMS answers building questions. Quality teams ask clinical ones.

Hospital BMS platforms run plant well. The gap is the question being asked of the data. Aqueduct reads the same points and answers in the language of the people who carry the risk.

Who is askingWhat the BMS answersWhat they actually need to know
Theater managerIs AHU-2 running?Is Theater 2 ready for the next case right now?
Infection prevention leadWhich panel has a pressure alarm?Did every isolation room hold containment all week?
Quality and accreditationWhat is the fault code?Where is a month of continuous theater and NICU evidence?
Renal unit leadIs the RO plant on?Has the treatment train drifted since the last water test?
Director of facilitiesWhich AHU has a filter alarm?Which plant fault is about to reach a clinical room?
Finance and ESGWhat does the energy dashboard show?What is energy and water per occupied bed, by hospital?
How it rolls out

Start with the theater and NICU block. Clone it across the network.

The theater and neonatal block has clear boundaries, a defined set of AHUs and the highest stakes, so value is visible to clinicians early. Networks such as one of India's top hospital chains, with 22 hospitals and 9 clinics, need the same safety definition at every site, so the first block becomes the template.

1
Weeks 1 to 3

Survey and room register

A non-invasive walk of the block: AHUs serving critical rooms, pressure cascades, dialysis RO, UPS and generators, and the BMS points already exposed. Room classes and limits are agreed with your quality team.

2
Weeks 4 to 10

Data foundation

Edge gateway installed, BMS points mapped, retrofit pressure and air sensors added where missing. First live readings and alarms, with data kept on your network.

3
Weeks 10 to 16

Readiness and evidence

Room verdicts live for theaters, NICU and isolation. Evidence packs for a month of records are generated from the platform rather than assembled from logbooks.

4
After the first block

Predict, then scale

aQ PredictIQ on the AHUs and chillers behind clinical rooms. The room register and limits are cloned to the next hospital, and newly acquired sites are measured against the same definition from day one.

What each seat gets

One record, read six ways.

Theater and ICU managers

A ready or not ready state per room before each case, with the reason in plain words when it is not.

Infection prevention

Continuous containment and humidity history for every isolation room and theater, not samples from rounds.

Quality and accreditation

Evidence packs exported on demand for surveys. The surveyor and your team judge compliance; Aqueduct supplies the measurements.

Learn more

Facilities and biomedical engineering

Plant faults linked to the rooms they threaten, ticketed into your CMMS and confirmed closed.

Learn more

Energy and finance

HVAC tuning proposals backed by proof that clinical conditions held while the change was made, and savings confirmed at the meter.

Learn more

Group leadership

Energy and water per occupied bed, compared across hospitals, ready for board and ESG reporting.

Proof

Proven in live sites across sectors.

Anonymized results, verified at the meter.

Deployed
275+

sites in 21 countries run on Aqueduct.

Healthcare
22 hospitals

and 9 clinics in one of India’s top hospital chains.

Airports
Top 25

US airport running water intelligence on Aqueduct.

Real estate
20M+ sq ft

of commercial real estate under Aqueduct.

Customer names withheld. Every result is anonymized.
Questions

Common questions

It can. Aqueduct can replace a BMS, BAS or EMS, or work across the ones you keep. Clinical systems stay separate.

It keeps continuous temperature and flow records at the points your program names, flags excursions, routes the fix into your CMMS and retains the evidence. You run the program; Aqueduct supplies the measurements.

Yes. Aqueduct can be deployed on-prem, with AI on NVIDIA infrastructure, for sites that cannot send data out.

No. Aqueduct holds whatever limits your protocol specifies, whether that is ASHRAE 170, NABH aligned values or your own infection control policy. Each room class carries its own bands, and changes to them are logged.

No. It measures the environment and utilities in clinical spaces: air, water and power. It does not read patient records, nurse call or bedside devices.

That is the point of measuring per room. Setpoint and airflow changes are made with continuous proof that each room stayed inside its limits, so engineering can tune with evidence rather than avoid the plant. Control changes happen only where control is enabled, with owner approval.

It stays in the record with its start, duration, peak, cause, the ticket raised and the time back in range. That record is what a surveyor or your quality team reviews later.

Each new site is mapped to the same room classes and limits as the rest of the network, whatever BMS it arrived with. Its scores are visible against the group standard as soon as its points are connected.

No. Online measurements such as conductivity and RO performance show drift between scheduled tests. Your chemical and microbiological testing program stays in place, and its results remain with your renal team.

See Aqueduct on your own facility.

Bring a site, a utility bill or a question. We will show you where the loss is.