For building, MEP and controls engineers

Building analytics software for engineers, with live twins and real control

Building analytics software for engineers turns meter, sensor and controller points into diagnosis. Aqueduct models the real system block by block, a water balance, an electrical single line and per-RTU component states, reads BACnet, Modbus, MQTT and LoRaWAN, diagnoses faults, and controls equipment where control is enabled with owner approval, with every command logged.

Powered by aQ Core, aQ EnergySmart and Smart Controls
Rooftop cooling towers in a city
Circuit breakers in a distribution board
Energy balance · active power
412Grid+146Solar=338HVAC+99Light+16Loss
Power factor 0.96Carbon today 1.9 t
Demo data

A model of the real system, so every fault has a location and a cause.

Live digital twins

The system modeled block by block, the way it is installed

  • Water balance equation

    Supply, floors, fire system, RO feed and unaccounted loss shown as one live equation.

  • Electrical single line

    Sources, switchboard and feeders with power factor and loading against rated kVA.

  • RTU states

    Mode, economizer, cooling, heating and fans shown as components, not raw telemetry points.

Substation lit at night
Energy balance · active power
412Grid+146Solar=338HVAC+99Light+16Loss
Power factor 0.96Carbon today 1.9 t
Demo data
Diagnosis

Faults explained, ticketed and confirmed closed

  • Plain-language findings

    Each fault states the component, the evidence and the likely cause in operator language.

  • Early signs of failure

    Vibration, sound signature and energy drift schedule maintenance before the equipment stops.

  • Confirmed by the twin

    After the repair, attainment and airflow must return to target before the fault closes.

Plant equipment in an industrial hall
Compressor 2 · condition
7.1 mm/s vibration
Maintenance scheduled before failure
Demo data
Control

Commands with lockouts, schedules and an audit trail

  • Two control paths

    LoRaWAN relays for simple loads, field device controllers over Modbus or BACnet for complex equipment.

  • Occupancy-driven rules

    Automations trigger on device thresholds or on site, zone or floor occupancy.

  • Command history

    Every command and its result recorded, with lockouts that block short cycling.

Control panel switches
Command history · RTU-2
Occupied mode07:00 · executed
Economizer on07:12 · executed
Lockout active07:13 · held
Demo data
Old way vs the Aqueduct way

Building engineering, before and after Aqueduct

The old way
  • Thousands of points, no model of how they connect.
  • Every vendor brings a protocol and a separate login.
  • Faults arrive as hot calls from occupants.
  • Overrides at the panel leave no record.
  • Savings from a retrofit are estimated, not measured.
The Aqueduct way
  • A live twin models the system block by block.
  • BACnet, Modbus, MQTT and LoRaWAN on one data layer.
  • Faults arrive diagnosed, located and ticketed.
  • Every command is logged with its result.
  • Savings are measured against a weather-normalized baseline.
Problems

What engineers fight with today

The data exists. Getting it into one model you can reason about is the hard part.

01

Points without a model

Trend logs list thousands of points with cryptic names and no picture of how the system actually connects.

02

Every vendor, a new protocol

BACnet here, Modbus there, pulse meters on the water side, and a LoRaWAN pilot nobody integrated.

03

Faults found by complaint

A stuck damper or a short-cycling compressor shows up as a hot-call ticket, not as a diagnosis.

04

Control without an audit trail

Overrides are made at the panel and nobody can say later what changed, when, or whether it executed.

What you get

What engineers get from Aqueduct

A model of the real system, built block by block to match what is installed.

Water digital twin

Main Supply equals All Floors plus Fire System plus RO Feed plus Unaccounted Loss, live.

Learn more

Electrical single line

Grid, solar and backup sources balanced against HVAC, lighting, plugs, services and losses.

Learn more

RTU component states

Damper, cooling, heating and fan states with setpoint attainment and comfort compliance.

Learn more

Open protocols

BACnet, Modbus, MQTT, M-Bus, pulse and LoRaWAN through gateways and field device controllers.

Learn more

Load disaggregation

Feeder and equipment loads separated so you see which system drives the curve.

Learn more

Audited control

Schedules, automations and lockouts, with command history showing what executed.

Learn more
Who it is for

Questions engineers ask

Controls engineer
“How does Aqueduct actually control equipment?”

Two ways only: LoRaWAN relay switches for simple loads such as fans, and a field device network controller speaking Modbus or BACnet to AHUs, RTUs, chillers and VAV boxes. Control runs only where enabled, with owner approval.

MEP engineer
“Can I specify Aqueduct into a new building?”

Yes. Aqueduct can be built in at design stage, so meters, sub-meters and controllers are specified once and the digital twin matches the drawings at handover.

Electrical engineer
“Does it show power quality or just kWh?”

Power monitoring devices report kW, kVAR, kVA, power factor, voltage, current and imbalance. The electrical twin shows loading against rated kVA per feeder.

Commissioning engineer
“How do I know a command actually executed?”

Command history records each command and its result, and lockout warnings block new commands while one is still being acted on, which protects equipment from short cycling.

Condenser fans seen from above
What we believe

Engineers should argue about the fix, not about whose data is right.

Talk to our team
How it works

How Aqueduct shows up in an engineer's week

An illustrative week for a controls engineer across several sites.

01

Monday

The fault log shows an RTU with low setpoint attainment over the weekend. The twin shows the economizer damper stuck at minimum.

02

Tuesday

A ticket with the diagnosis routes into the CMMS. After the repair, setpoint attainment recovers and the fault closes as confirmed.

03

Wednesday

An automation rule is built: when floor occupancy drops, raise the cooling setpoint. It runs where control is enabled, with owner approval.

04

Thursday

A compressor shows rising vibration and energy drift. Maintenance is scheduled before it fails.

05

Friday

The engineer asks aQ Assistant how this week's HVAC energy compares with the last four, and gets a table with a data quality note.

Go deeper

Features and industries engineers use most

The depth sits in these pages.

Digital twin

Water, electrical and RTU twins built to match the site.

Learn more

Peak demand management

Load sequencing and power factor against your tariff.

Learn more

Predictive maintenance

Vibration, sound signature and energy drift before failure.

Learn more

Data centers

Cooling load and power quality at the feeder.

Learn more

Manufacturing

Process water, compressed air and power at the line.

Learn more

Build it in

Specify Aqueduct at design with architects and MEP teams.

Learn more
Where engineers find the fault

The systems an engineer models, and what each one hides

Each block on the twin matches something installed. Here is what goes wrong quietly in each, what gets measured, and what Aqueduct does with it.

Chilled water plant

Where it goes wrong

Low delta T: pumps move more water for the same cooling and the plant loses efficiency

What we measure

Feeder kW, BTU meter flow, supply and return temperatures

What Aqueduct does

Trends delta T against load and kW per ton per chiller

Rooftop units

Where it goes wrong

Economizer stuck at minimum, units cooling empty floors

What we measure

Mode, damper position, supply air temperature, fan status

What Aqueduct does

Shows component states and setpoint attainment on the RTU twin

Air handlers

Where it goes wrong

Valves and dampers not following command, filters left in alarm

What we measure

Command against feedback, differential pressure, airflow

What Aqueduct does

Lists actuators that disagree with their command

Electrical distribution

Where it goes wrong

Poor power factor and feeders loaded far from rated kVA

What we measure

kW, kVAR, kVA, voltage, current, imbalance per feeder

What Aqueduct does

Draws the single line with loading and power factor per node

Domestic water

Where it goes wrong

Slow leaks and overflows that never trigger a threshold

What we measure

Main supply and sub-meters on floors, risers and lines

What Aqueduct does

Closes the water balance and tracks unaccounted loss

Treatment plant

Where it goes wrong

RO recovery falling as membranes foul, reuse assumed rather than measured

What we measure

RO feed, permeate, reject, TDS; STP inlet, treated flow, BOD out

What Aqueduct does

Puts recovery and STP efficiency on the same twin as supply

Rotating equipment

Where it goes wrong

Bearing wear and imbalance developing for weeks before a trip

What we measure

Vibration, sound signature, energy per unit of work

What Aqueduct does

aQ PredictIQ schedules maintenance before failure

Zones

Where it goes wrong

Comfort complaints with no record of what the zone actually did

What we measure

Zone temperature, CO2, occupancy

What Aqueduct does

Ties comfort compliance to the unit serving the zone

What engineers measure

The control and plant KPIs on the twin

The KPIs that separate a working control sequence from one that only looks fine on a graphic.

KPIHow it is derivedWhat a bad value usually means
Setpoint attainmentShare of time a unit holds its setpointUndersized capacity, a stuck damper or a fighting sequence
Comfort complianceShare of occupied time zones stay in bandControl is saving energy at the occupants' expense
Sequence exceptionsCount of steps that ran out of orderLogic changed at the panel or a sensor gone bad
Short-cycle eventsStarts within a short window of a stopTuning issue, now blocked by lockouts
kW per tonElectrical input against BTU meter cooling outputFouled condenser, low delta T or poor staging
Power factor and loadingPer feeder against rated kVAReactive penalty risk and badly placed correction
Unaccounted lossSupply minus every metered useA leak, an overflow or an unmetered connection
Working practice

How engineers use Aqueduct beyond fault finding

Commissioning evidence

Command history and component states show whether a sequence actually ran as designed after handover, not only on the test day.

Design-stage specification

Meters, sub-meters and controllers are specified once, so the twin matches the drawings at handover.

Learn more

Rules you build yourself

If and else logic on device thresholds or occupancy, with severity, scope and lockouts, running only where control is enabled with owner approval.

Clusters for real systems

Group an RTU with its zone sensors so the sensor reading informs the unit and the cluster is analyzed as one system.

Trusted at scale
Read the case studies
Deployed275+

sites in 21 countries run on Aqueduct.

Healthcare22 hospitals

and 9 clinics in one of India’s top hospital chains.

AirportsTop 25

US airport running water intelligence on Aqueduct.

Real estate20M+ sq ft

of commercial real estate under Aqueduct.

Manufacturing300 acres

FMCG manufacturing campus.

Food and dairyMajor dairy

operations run on Aqueduct.

Questions

Common questions

It is software that turns BMS, meter and sensor points into a model engineers can diagnose from. Aqueduct builds live digital twins of the water system, the electrical single line and individual RTUs, then runs fault detection and verified control on top of them.

Yes. Aqueduct talks BACnet and Modbus through a field device network controller, and also reads MQTT, M-Bus, pulse outputs and LoRaWAN devices. Data refreshes every 60 seconds.

A BMS graphic shows points on a picture. Aqueduct's twin models the physical system and its balance, for example Main Supply equals All Floors plus Fire System plus RO Feed plus Unaccounted Loss, so the gap itself becomes the diagnostic signal.

FDD acts after a fault: it finds, diagnoses and routes the fix, then confirms it. Predictive maintenance acts before failure: vibration, a new sound signature or energy drift schedules maintenance first.

Yes. The rule builder sets thresholds on a device or on site, zone or floor occupancy, with if and else logic and actions. Rules run only where control is enabled, with owner approval.

Yes. Aqueduct can be built in at design stage, so metering, sub-metering and controls are specified once and the digital twin matches the installed system at handover.

It can replace or work across the BMS. Field controllers stay as the control layer for equipment, and Aqueduct supervises, analyzes and commands them where control is enabled.

It divides electrical input on the chiller feeder by cooling output from BTU meter flow and header temperatures. Where feeders are not split per chiller, it reports plant-level efficiency instead.

A cluster groups devices and sensors so they operate and are analyzed as one system. For example, a pressure sensor linked to an RTU can trigger a filter change alert for that unit.

Yes. Component states on the twin and command history show each step, whether it executed and when, and sequence exceptions count the steps that ran out of order.

No. The twin is built block by block, and blocks without a reporting meter show as no data. Coverage grows as points are added, and the balance becomes more precise.

See Aqueduct on your own facility.

Bring a site, a utility bill or a question. We will show you where the loss is.