Use case: HVAC energy

HVAC energy optimization, baselined against weather and verified at the meter

HVAC energy optimization reduces the energy heating, cooling and ventilation use without losing comfort. Aqueduct baselines HVAC consumption against weather, finds faults and schedule waste, adjusts setpoints and schedules where control is enabled with owner approval, and verifies each saving at the meter against the weather-normalized baseline.

Powered by aQ EnergySmart and Smart Controls, built on aQ Core
Condenser fans seen from above
Site performance · this quarter
-8.4% vs expected
Weather normalizedBelow baseline
Demo data
Command history · RTU-2
Occupied mode07:00 · executed
Economizer on07:12 · executed
Lockout active07:13 · held
Demo data

Cut HVAC waste without cutting comfort, and prove the saving at the meter.

Fair baseline

HVAC energy compared with what the weather demands

  • Degree-day regression

    Usage regressed on cooling and heating degree days gives an expected value for every period.

  • Per unit and per feeder

    HVAC feeders and units are separated, so the wasteful one stands out.

  • Day-one results

    Uploading 6 to 12 months of bills sets the baseline before new metering is installed.

Large industrial fans on a plant wall
Site performance · this quarter
-8.4% vs expected
Weather normalizedBelow baseline
Demo data
Find the waste

Faults and schedules that burn energy quietly

  • Component states

    The RTU twin shows economizer, cooling, heating and fans as components, not raw points.

  • Control quality KPIs

    Setpoint attainment, comfort compliance and sequence exceptions show where control is slipping.

  • Plain-language cause

    Each finding names the failing component, the evidence behind it and a recommended fix in plain language.

Rooftop cooling towers in a city
AHU-1 · fault
Supply fan stopped08:02
Failed rotor shaft08:03
Routed to CMMS08:04
Airflow confirmed11:40
Demo data
Act and verify

Changes made with approval, savings measured

  • Schedules and setpoints

    Adjusted where control is enabled, with owner approval and lockouts against short cycling.

  • Command history

    Every command and its result are recorded, so controls claims stand up to M&V and procurement review.

  • Verified saving

    HVAC energy is measured below baseline after the change, and the saving is priced from your own rates.

Control panel switches
Command history · RTU-2
Occupied mode07:00 · executed
Economizer on07:12 · executed
Lockout active07:13 · held
Demo data
Old way vs the Aqueduct way

HVAC energy, before and after Aqueduct

The old way
  • Units run to schedules nobody has checked in years.
  • A stuck economizer wastes energy for months.
  • A hot month hides whether the plant got worse.
  • Panel overrides stay in place indefinitely.
  • Retrofit savings come from the vendor's proposal.
The Aqueduct way
  • Schedules follow occupancy where control is enabled.
  • The RTU twin flags the stuck economizer.
  • Degree-day baselines separate weather from waste.
  • Command history shows every change and its result.
  • Savings are verified at the meter against baseline.
Problem

Where HVAC energy goes to waste

HVAC is usually the largest controllable load, and the hardest to see clearly.

01

Schedules that drift

Units run to schedules set years ago, heating and cooling empty floors at night and on weekends.

02

Faults that waste quietly

A stuck economizer or a damper at minimum keeps comfort just about right while energy climbs.

03

No fair baseline

Energy rises in a hot month and nobody knows whether the plant or the weather is to blame.

04

Overrides that stay

Someone overrides a setpoint at the panel and it stays that way for months.

One incident, start to finish

How Aqueduct optimizes HVAC energy

One HVAC saving, from signal to verification.

Monitor

HVAC sub-meters, BMS points and RTU or AHU controllers report into aQ Core every 60 seconds.

Measure

A weather-normalized baseline is set by regression on usage plus cooling and heating degree days.

Identify

Energy runs above baseline overnight. The RTU twin shows the unit cooling an unoccupied floor with the economizer stuck.

Act

The fault routes to your CMMS, and the schedule is tied to occupancy where control is enabled with owner approval.

Verify

HVAC energy returns below baseline, the saving is priced from your rates, and the result becomes the new baseline.

On site

What it needs on site

Existing BMS points and controllers connect over BACnet or Modbus. New devices are installed through partners.

DeviceWhat it measures or doesWhy it matters
HVAC sub-meters or power meterskW and kWh per feeder or unitShows what HVAC actually uses against baseline
BMS points or field device controllerSetpoints, modes, damper and fan statesFeeds the RTU and AHU twin, and enables control
Zone temperature and CO2 sensorsComfort and ventilation by zoneKeeps savings from costing comfort or air
Occupancy sensors or schedulesWhether a zone is in useLets equipment follow real use
Utility bills, 6 to 12 monthsHistorical use and ratesDay-one baseline and savings in money
Large ducts in a plant space
What we believe

The cheapest kilowatt-hour is the one a stuck damper no longer wastes.

Talk to our team
Problem, solution, impact

Outcome

What changes when HVAC runs against a fair baseline.

The problemHow Aqueduct solves itThe impact
Energy

HVAC waste hidden inside the monthly total.

HVAC baselined against weather and tracked per unit.

Energy savings verified at the meter against a weather-normalized baseline.

Air

Savings made by cutting fresh air.

CO2 and comfort tracked alongside energy.

Savings that hold air quality in range.

Operations

Faults found by hot calls.

Faults diagnosed from component states and routed to the CMMS.

Fewer complaints and confirmed repairs.

Personas

Who cares about this

The seats that ask for this first.

Building, MEP and controls engineers

RTU and AHU component states, rules and command history.

Learn more

Facilities managers and directors

Faults and schedule waste routed as clear tickets.

Learn more

CFOs and finance teams

HVAC savings priced and verified against baseline.

Learn more
Where HVAC energy leaks

Eight places HVAC energy is wasted without anyone noticing

Most HVAC waste keeps the building comfortable enough that nobody complains. That is exactly why it lasts.

Schedules

Where it goes wrong

Equipment conditioning empty floors at night and on weekends

What we measure

Runtime against occupancy

What Aqueduct does

Ties schedules to occupancy where control is enabled

Economizers

Where it goes wrong

Damper stuck at minimum, so free cooling is never used

What we measure

Damper position, outdoor and mixed air temperature

What Aqueduct does

RTU twin shows the economizer state

Simultaneous heating and cooling

Where it goes wrong

Reheat fighting cooling in the same zone

What we measure

Heating and cooling states per unit

What Aqueduct does

Flags units doing both

Chilled water delta T

Where it goes wrong

Low delta T makes pumps and chillers work harder for the same load

What we measure

Supply and return temperatures, flow

What Aqueduct does

Trends delta T against load

Overrides

Where it goes wrong

Panel overrides left in place for months

What we measure

Setpoint and mode against schedule

What Aqueduct does

Lists units off their programmed state

Ventilation

Where it goes wrong

Outdoor air at design rate for a few people

What we measure

CO2 and occupancy by zone

What Aqueduct does

Demand controlled ventilation where enabled

Filters and coils

Where it goes wrong

Fan power rising as filters load

What we measure

Differential pressure, fan kW

What Aqueduct does

Condition-based filter alerts

Short cycling

Where it goes wrong

Repeated starts waste energy and wear compressors

What we measure

Start and stop events

What Aqueduct does

Lockouts block commands mid-action

By the numbers

Why cooling dominates in hot climates

80%

up to this share of a UAE building's electricity demand goes to cooling

Source: Heriot-Watt University: Retrofit options to reduce climate change impacts on UAE buildings
30%

Dubai's target cut in electricity and water demand by 2030, against business as usual

Source: MEED: Dubai updates energy savings target
68 to 75 F

the ASHRAE 170 design temperature range for operating rooms, an example of a band HVAC must hold while saving

Source: ASHRAE Journal: Conditioning for the environment of critical care hospital operating rooms
How it works

How a saving is proven, not claimed

01

Baseline the HVAC load

HVAC feeders or unit meters are baselined by regression on usage plus cooling and heating degree days, using bills where history is missing.

02

Find the cause

The twin shows whether excess energy comes from a schedule, a stuck component or an override, and names it.

03

Change it with approval

Schedules and setpoints change where control is enabled, with owner approval. Lockouts prevent short cycling.

04

Watch comfort and air

Comfort compliance and CO2 are tracked alongside energy, so a saving that costs comfort shows immediately.

05

Verify and reset

Energy below baseline is priced from your rates and becomes the new baseline, with command history as the audit trail.

Fault signatures

How common HVAC faults look on the twin

Each fault leaves a recognizable pattern in component states and energy. These are the ones found most often.

FaultWhat the data showsUsual fix
Stuck economizerDamper at minimum while outdoor air is cool enough to useActuator or linkage repair
Schedule driftOccupied mode at night or weekends with no occupancySchedule correction or occupancy rule
Override left in placeSetpoint or mode differs from the programmed state for daysRelease the override, log the change
Simultaneous heating and coolingHeating and cooling active in the same unit or zoneSequence or deadband correction
Low delta TChilled water return close to supply under loadCoil valve, bypass or flow balancing
Loaded filterDifferential pressure and fan power rising togetherFilter change on condition
Short cyclingRepeated starts within minutesTuning, with lockouts in place
Trusted at scale
Read the case studies
Deployed275+

sites in 21 countries run on Aqueduct.

Healthcare22 hospitals

and 9 clinics in one of India’s top hospital chains.

AirportsTop 25

US airport running water intelligence on Aqueduct.

Real estate20M+ sq ft

of commercial real estate under Aqueduct.

Manufacturing300 acres

FMCG manufacturing campus.

Food and dairyMajor dairy

operations run on Aqueduct.

Questions

Common questions

Measure HVAC consumption, set a weather-normalized baseline, then fix faults, tighten schedules and match operation to occupancy. Aqueduct does this continuously, acts where control is enabled with owner approval, and verifies each saving at the meter.

It is the energy HVAC should use given the weather. Aqueduct builds it by regression on historical usage plus cooling and heating degree days, so savings are not confused with a mild season.

Yes, where control is enabled with owner approval. Aqueduct controls through LoRaWAN relay switches for simple loads and a field device network controller over Modbus or BACnet for RTUs, AHUs, chillers and VAV boxes.

It should not. Aqueduct tracks comfort compliance, setpoint attainment and CO2 alongside energy, so savings that would push a zone out of range are visible immediately.

Lockout warnings block new commands while an earlier command is still being acted on, which protects equipment from short cycling. Command history records every command and its result.

No. Aqueduct can work across your existing BMS, replace it, or be built into new construction. Existing BMS points connect over BACnet or Modbus.

Usually with schedules and overrides, because they cost nothing to fix. Overnight and weekend HVAC energy against baseline shows quickly whether equipment runs when nobody is there.

The RTU twin compares damper position with outdoor and mixed air temperatures. A damper held at minimum while outdoor air could cool for free is flagged as a fault.

Yes. The baseline accounts for cooling and heating degree days, so a hotter year raises expected use and the saving is measured against that higher expectation.

It measures kW per ton and delta T against load and flags plant faults. Control of chillers runs through a field device network controller, where control is enabled with owner approval.

It can measure HVAC energy from feeder or unit meters and find waste against baseline. Diagnosing components and making changes needs BMS points or a field device network controller.

See Aqueduct on your own facility.

Bring a site, a utility bill or a question. We will show you where the loss is.