ASHRAE 90.1

ASHRAE 90.1 controls and metering, proven in operation

ASHRAE 90.1 is the energy standard for buildings other than low-rise residential, and the basis for most US commercial energy codes. It covers envelope, HVAC, service water heating, power, lighting and controls. Aqueduct shows whether the required controls keep running after handover: schedules, setbacks, economizers and demand-controlled ventilation, plus metered energy by end use. Your engineer owns design compliance.

Powered by aQ EnergySmart, built on aQ Core
Air conditioning units on a building wall
AHU-1 · fault
Supply fan stopped08:02
Failed rotor shaft08:03
Routed to CMMS08:04
Airflow confirmed11:40
Demo data
Energy balance · active power
412Grid+146Solar=338HVAC+99Light+16Loss
Power factor 0.96Carbon today 1.9 t
Demo data

The controls designed into a building, still working long after handover.

Controls in operation

Schedules, setbacks and economizers checked every day

  • Run states tracked

    Equipment running outside occupied hours is flagged against the schedule the building should follow.

  • Economizer faults

    Stuck dampers and disabled economizers are diagnosed from the unit's own states and outdoor conditions.

  • Lockouts respected

    Lockout warnings hold new commands while one is executing, which prevents short cycling.

Condenser fans seen from above
AHU-1 · fault
Supply fan stopped08:02
Failed rotor shaft08:03
Routed to CMMS08:04
Airflow confirmed11:40
Demo data
Energy by end use

Metering that splits energy the way the standard does

  • End-use split

    HVAC, lighting, plugs and services are metered as separate terms in the energy balance.

  • Live single line

    Sources, switchboard and feeders appear on one electrical twin, with loading against rated capacity.

  • Peak demand

    Demand peaks are recorded and loads can be sequenced so they do not all start together.

Circuit breakers in a distribution board
Energy balance · active power
412Grid+146Solar=338HVAC+99Light+16Loss
Power factor 0.96Carbon today 1.9 t
Demo data
Design versus reality

Modeled savings checked against measured consumption

  • Normalized comparison

    Actual use is compared with a weather-normalized baseline, so seasons do not distort the gap.

  • Drift explained

    When consumption rises above expectation, the finding names the feeder or unit responsible.

  • Verified result

    After a fix, the meter confirms the saving before anyone reports it.

Concrete arches
Site performance · this quarter
-8.4% vs expected
Weather normalizedBelow baseline
Demo data
Old way vs the Aqueduct way

Energy code performance, before and after Aqueduct

The old way
  • Controls pass commissioning, then quietly get overridden.
  • Economizers stick closed and nobody notices for a season.
  • One utility meter hides which end use is rising.
  • The energy model is never compared with real consumption.
  • Setbacks vanish after a controller reset.
The Aqueduct way
  • Overrides and lost schedules are flagged the day they happen.
  • Economizer faults are diagnosed and routed to your CMMS.
  • HVAC, lighting and plug loads are metered separately.
  • Measured use is compared with a weather-normalized expectation.
  • Schedules are restored where control is enabled, with owner approval.

What ASHRAE 90.1 is and who it applies to

ASHRAE Standard 90.1 sets minimum energy efficiency requirements for the design and construction of new buildings, additions and major alterations, excluding low-rise residential. It is published jointly by ASHRAE and IES, updated on a three-year cycle, and adopted by reference in many US state and local energy codes. Green building programs, including LEED, use its Appendix G Performance Rating Method to compare a design against a baseline building.

The standard covers the building envelope, HVAC, service water heating, power, lighting and other equipment. Compliance can follow a prescriptive path or a performance path such as the Energy Cost Budget method or Appendix G. Its mandatory provisions include HVAC controls such as off-hour shutdown and setback, and recent editions include energy monitoring provisions for larger buildings.

Design compliance is checked at permit and commissioning. What the code cannot see is whether those controls are still working two years later. That is where Aqueduct supplies evidence.

Evidence map

ASHRAE 90.1 requirement areas and the evidence Aqueduct supplies

Operational evidence that the energy measures designed in are still delivering.

Requirement areaEvidence Aqueduct supplies
Off-hour controls and setbackEquipment run states against occupancy schedules, with after-hours operation flagged
EconomizersEconomizer and outdoor air damper states from connected RTUs and AHUs, with faults diagnosed
Demand-controlled ventilationZone CO2 and occupancy with the ventilation response recorded
Energy monitoringMetered consumption by end use: HVAC, lighting, plugs and services, from sub-meters and the electrical twin
Service water heatingGas and electricity to water heating metered, with hot water flow where meters exist
Performance path trackingActual consumption compared with a weather-normalized baseline, so the modeled design can be checked against reality
How it works

How Aqueduct supplies 90.1 evidence in operation

The controls in the drawings, checked against what the equipment does.

01

Connect the equipment

RTUs, AHUs, chillers and VAV boxes connect through a field device network controller over BACnet or Modbus. Meters connect over LoRaWAN, Modbus, M-Bus or pulse outputs.

02

Model the RTU and the building

The equipment digital twin shows dampers, economizer, cooling, heating and fans as states, and the electrical twin balances sources against end uses.

03

Find what drifted

Setbacks overridden, economizers stuck closed, schedules lost after a controller reset. Each becomes a diagnosed finding routed to your CMMS.

04

Restore and verify

Where control is enabled, with owner approval, schedules and setpoints are restored. The meter confirms the energy result.

Rooftop cooling towers in a city
What we believe

An energy code describes a building on day one. Operations decide the rest.

Talk to our team

What stays with your engineer and the authority

Aqueduct is not a code compliance tool for design.

Design and permit documents

Envelope, lighting power and equipment efficiency compliance are shown by the design team at permit.

Energy modeling

Appendix G and Energy Cost Budget models are prepared by energy modelers. Aqueduct supplies measured data to compare against them.

Commissioning sign-off

Commissioning agents and the authority having jurisdiction confirm compliance. Aqueduct keeps the operational record afterward.

Standards and regulations

Related standards

Often referenced with 90.1.

IECCASHRAE 62.1 ASHRAE Guideline 36ASHRAE 90.4 Title 24, Part 6 LEED energy and atmosphere
Sections that need data

The 90.1 provisions that drift after handover

ASHRAE 90.1 is checked at design and permit. The controls it requires, though, are exactly the ones that get overridden in year two. These are the sections worth watching in operation.

01 / 05

Section 6: HVAC controls

90.1 requires off-hour controls, setback, optimum start, zone dead bands and limits on simultaneous heating and cooling. Each is easy to defeat with an override that nobody removes.

  • Equipment running outside schedules
  • Heating and cooling active in the same zone
  • Setbacks disabled after complaints
Data needed
schedules, setpoints and equipment state
Source
BMS points over BACnet
Aqueduct
sequence exceptions flagged per unit
02 / 05

Section 6: Air economizers

Where required, economizers must bring in outdoor air for free cooling when conditions allow. Stuck dampers and bad sensors turn them off without anyone noticing.

  • Damper position against outdoor temperature
  • Mixed air temperature consistency
  • Economizer lockouts that never clear
Data needed
damper, outdoor and mixed air temperatures
Source
RTU and AHU controllers
Aqueduct
economizer faults by unit
03 / 05

Section 9: Lighting controls

90.1 requires automatic shutoff, occupancy sensing in many spaces and daylight responsive controls. Sub-metering lighting shows whether they work.

  • Lighting load after hours
  • Lighting load in unoccupied zones
  • Daylight zones that never dim
Data needed
lighting load and occupancy
Source
lighting feeder sub-meters, PIR sensors
Aqueduct
after-hours lighting flagged
04 / 05

Section 8: Electrical energy monitoring

Recent editions require many buildings to measure and record electrical energy by end use, such as HVAC, lighting and plug loads, and to report it. That is a data system requirement, not just a meter.

  • End-use sub-metering
  • Interval recording and retention
  • Reports building occupants can use
Data needed
energy by end use at interval resolution
Source
CT sub-meters on feeders
Aqueduct
end-use trends and reports
05 / 05

Appendix G: Performance Rating Method

Projects using the performance path model a proposed design against a baseline. Once occupied, measured energy shows whether the building runs as modeled.

  • Measured EUI against modeled EUI
  • End-use comparison where sub-metered
  • Weather-normalized for a fair comparison
Data needed
measured energy by end use and weather
Source
meters and weather per site
Aqueduct
measured against modeled, normalized
How it rolls out

Keeping a 90.1 building performing as permitted

For new buildings at handover, or existing buildings checking whether their controls still do what the code required.

1
Week 1

Collect sequences and schedules

Pull the sequences of operation, schedules and lighting control narrative from the design and commissioning documents.

2
Weeks 2 to 4

Connect BMS and sub-meters

Read controllers over BACnet or Modbus and connect end-use sub-meters for HVAC, lighting and plug loads.

3
Weeks 4 to 8

Test controls in operation

Check schedules, setbacks, economizers and lighting shutoff against the data, and route each fault to maintenance.

4
Month 3 onward

Watch for drift

Sequence exceptions, setpoint attainment and after-hours load are tracked monthly so overrides do not become permanent.

Section to meter map

ASHRAE 90.1 sections mapped to meters and sensors

Most points already exist in the BMS. Sub-meters fill end-use gaps.

SectionWhat to measureMeters and sensorsAqueduct output
5 EnvelopeHeating and cooling response to weatherZone temperature sensors, weather per siteWeather sensitivity per building
6 HVAC off-hour controlsEquipment runtime against scheduleFan and compressor status pointsAfter-hours runtime
6 Simultaneous heating and coolingHeating and cooling valve or stage statesAHU and VAV controller pointsConflict alerts
6 EconomizersDamper and air temperaturesRTU and AHU controllersEconomizer fault flags
7 Service water heatingHeater energy and temperaturesHeater sub-meters, temperature sensorsStandby loss and schedule checks
8 Electrical monitoringEnergy by end useCT sub-meters on feedersEnd-use trends and reports
9 Lighting controlsLighting load and occupancyLighting sub-meters, PIR sensorsAfter-hours and unoccupied lighting
Appendix GWhole-building energyUtility and sub-meters, weatherMeasured against modeled EUI
What we find

The 90.1 controls most often defeated in operation

Permanent overrides

A temporary override on an air handler becomes the new normal and the unit runs every night. Sequence exceptions make it visible.

Economizers locked out

A failed outdoor air sensor locks the economizer out, so mechanical cooling runs on mild days the design expected to cool for free.

Lighting left on

Occupancy sensors disabled or mis-set keep lighting on in empty spaces. Lighting sub-meters show load where nobody is present.

Sources2 references cited on this page
  1. ASHRAE Standard 90.1
  2. US DOE Building Energy Codes Program
Trusted at scale
Read the case studies
Deployed275+

sites in 21 countries run on Aqueduct.

Healthcare22 hospitals

and 9 clinics in one of India’s top hospital chains.

AirportsTop 25

US airport running water intelligence on Aqueduct.

Real estate20M+ sq ft

of commercial real estate under Aqueduct.

Manufacturing300 acres

FMCG manufacturing campus.

Food and dairyMajor dairy

operations run on Aqueduct.

Questions

Common questions

ASHRAE 90.1 is the energy standard for buildings except low-rise residential, covering envelope, HVAC, water heating, power, lighting and controls. Many US commercial energy codes adopt it by reference. Aqueduct helps show that its controls keep working in operation.

Compliance applies to new buildings, additions and major alterations in jurisdictions whose energy code references it, which covers most US commercial construction. The design team and the authority having jurisdiction confirm compliance; Aqueduct supplies operational evidence afterward.

Recent editions include energy monitoring provisions for larger buildings, recording consumption by end use. Aqueduct meters HVAC, lighting, plug and service loads and presents them on a live electrical digital twin. Check the edition your jurisdiction adopted for the exact rule.

Appendix G is the Performance Rating Method, which compares a proposed design with a baseline building model. It is used for performance compliance and by LEED. Aqueduct supplies measured consumption so modeled savings can be checked against what the building actually uses.

Aqueduct reads economizer, damper, fan and setpoint states from connected RTUs and AHUs over BACnet or Modbus. Faults such as a stuck economizer or an overridden setback are diagnosed and routed to your CMMS.

No. Aqueduct does not certify code compliance. It keeps the controls designed into the building working and verifies the energy result at the meter against a weather-normalized baseline.

It can replace or work with your BMS, BAS or EMS. Many sites keep the BMS and let Aqueduct read across it, act where control is enabled with owner approval, and verify the result.

The edition adopted by your state or city energy code at the time of permit applies. Adoption varies widely, so check with the authority having jurisdiction.

Monitoring requires measuring and recording energy by end use and making it available, not only installing meters. Aqueduct records and reports the data from the sub-meters.

An operator overrides a schedule or setpoint to fix a complaint and nobody removes it. Aqueduct tracks sequence exceptions so overrides are visible and can be reversed.

Yes. Enter the modeled annual or monthly energy and Aqueduct compares it with weather-normalized measured consumption, by end use where sub-meters exist.

See Aqueduct on your own facility.

Bring a site, a utility bill or a question. We will show you where the loss is.